Fault Diagnosis and Analysis of Stable-nail Discharge in 500kV Transformer
A partial discharge fault was diagnosed by oil chromatographic analysis of a 500 kV transformer in operation.It was found that the fault was caused by partial discharge of a loose stable nail through fault analysis and dismantlement check.This kind of faults are analyzed theoretically and experientially to prevent the fault from worsening or even resulting in accident of transformer.