ZHANG Ben-huang1, LI Heng-zhen1, LIU Gang1, et al. Study on the Rule of Insulator Contamination Accumulation of Various Landforms in the Pearl River Delta[J]. High voltageapparatus, 2012, 48(4): 1-6.
ZHANG Ben-huang1, LI Heng-zhen1, LIU Gang1, et al. Study on the Rule of Insulator Contamination Accumulation of Various Landforms in the Pearl River Delta[J]. High voltageapparatus, 2012, 48(4): 1-6. DOI: 10.13296/j.1001-1609.hva.2012.04.002.
Study on the Rule of Insulator Contamination Accumulation of Various Landforms in the Pearl River Delta
This article selects four test sites in the Pearl River Delta in China on the electric transmission line of 220 kV
in order to study the rules of insulator contamination accumulation of various landforms in the Pearl River Delta
the change of ESDD and NSDD are analyzed combining the distribution of precipitation and the urban heat island effect.According to the study: ESDD of the insulator is much easier to be affected by the rainfall than NSDD;both the rainfall and pollution source are the key factors of the insulator contamination accumulation;the highest insulator contamination will be appeared before the first rainfall of the rainy season;there are many differences of the insulator contamination accumulation rules in various landforms