REN Shu1, HE Wei1, YANG Fan1, et al. Analysis and Calculation for the Capacitive Coupling of the AC and DC Transmission Lines on One Tower[J]. High voltageapparatus, 2012, 48(4): 39-45.
REN Shu1, HE Wei1, YANG Fan1, et al. Analysis and Calculation for the Capacitive Coupling of the AC and DC Transmission Lines on One Tower[J]. High voltageapparatus, 2012, 48(4): 39-45. DOI: 10.13296/j.1001-1609.hva.2012.04.008.
Analysis and Calculation for the Capacitive Coupling of the AC and DC Transmission Lines on One Tower
More and more attentions were concentrated on the development of ultra-high voltage(UHV) transmission line techniques.To solve the land occupation
building the UHV AC and DC transmission lines in the same tower is investigated by some experts.In this paper the capacitive coupling interference between the AC and DC transmission lines is calculated when they are erected in the same tower
the interference for different situation is analyzed
and based on the interference
measures to shield the interference are presented in the end.Results indicate that the induced voltage in the DC transmission lines depends on the arrangement of AC transmission lines
the vertical distance betwee
n the AC and DC transmission lines and phase of three phase AC have influence on the capacitive coupling effects.The induced voltage decreases with the increase of the distance.To restrain the induced voltage on the DC transmission lines the anti-phase of double circuit technique can be adopted.By using drum arrangement in the AC transmission lines
the induced voltage on the DC transmission lines can be decreased by 46.8%
and using ground wire can decrease the induced voltage by 7%
Calculation and Measurement Analysis for Induced Voltage and Current of 500 kV/220 kV Mixed-voltage and Four-circuit Transmission Lines on the Same Tower
Analysis on Influence of Different Aluminum Sheath Structure on Electrical Characteristics of Cable
Development and Project Application of Live Ice-melting System for UHVDC Transmission Lines
Characterization of Short-circuit Fault Voltage Distribution on Load Side of Cable-GIL Hybrid System
Analysis of loop current and temperature rise of GIS shell of ±200kV converter station based on field-circuit coupling
Related Author
HUANG Shiyang
NING Linru
CHEN Xiao
WANG Chenxing
LIN Tao
PENG Zhaowei
XU Dangguo
LI Yamei
Related Institution
Beijing Power Transmission and Transformation Co., Ltd.
State Grid Jibei Electric Power Co., Ltd.
State Grid Jibei Electric Power Co., Ltd. Electric Power Science Research Institute
State Grid Jiangsu Kunshan Electric Power Company Limited