LIU Yong1, CHEN Hao2, XIONG Bin1. Analysis on the Two-point Earthing Faults of CVT Secondary Side[J]. High voltageapparatus, 2012, 48(4): 111-114. DOI: 10.13296/j.1001-1609.hva.2012.04.021.
Analysis on the Two-point Earthing Faults of CVT Secondary Side
It is specified in the regulations that the secondary circuit in PT can have one point grounded.Besides that earthing by zinc oxide varistor in switch yard is often applied in practice.In this paper
based on the analysis on the protection mis-operation induced by the broken down of zinc oxide vaistor in the secondary circuit of CVT
it is found in terms of wave ananlysis that when the zinc oxide varistor is broken down
two points will be grounded
and the protections will receive wrong voltage value
which will lead to protection mis-operation or protection refusal-operation.Finally
the suggestions for eliminating the corresponding potential dangers are provided.