CHEN Zhong-ren1, HUANG Jian1, ZHOU Cheng-hong2. Analysis and Countermeasures of a Kind of PASS Switchgear Fault[J]. High voltageapparatus, 2012, 48(4): 119-121.
CHEN Zhong-ren1, HUANG Jian1, ZHOU Cheng-hong2. Analysis and Countermeasures of a Kind of PASS Switchgear Fault[J]. High voltageapparatus, 2012, 48(4): 119-121. DOI: 10.13296/j.1001-1609.hva.2012.04.023.
Analysis and Countermeasures of a Kind of PASS Switchgear Fault
A kind of imported PASS switchgear which was installed in Huangchuan substation had a fault that it could not switch on.Fault analysis shows that ratcheting worn and spring fatigue in switchgear machinery box are main causes.The corresponding countermeasures of replacing ratchet and adjusting the angle of flange plate make switch-on spring’s energy storage travel extend.This guarantees the spring to store energy effectively and solves the problem that the switch can not switch on.These countermeasures save maintenance costs and deserve the correlative technicians’ reference.