YAO Xiu1, JI Sheng-chang2, Luis Herrera1, et al. Series DC Arc Characteristic Study and the Application in Fault Recgnition[J]. High voltageapparatus, 2012, 48(5): 6-10.
YAO Xiu1, JI Sheng-chang2, Luis Herrera1, et al. Series DC Arc Characteristic Study and the Application in Fault Recgnition[J]. High voltageapparatus, 2012, 48(5): 6-10. DOI: 10.13296/j.1001-1609.hva.2012.05.003.
Series DC Arc Characteristic Study and the Application in Fault Recgnition
DC arc fault introduces major safety concerns in a wide variety of power electronic applications.However
the randomness and instability of DC arc makes it difficult to be detected.In this paper
an experimental system to study the characteristics of series DC arc was designed and different tests were conducted in order to determine the influence of different factors to the arc such as gap length
current
etc.During the experiments
the load current was varied from 6 A to 30 A and DC source voltage was changed from 75 V to 300 V.Also
DC arc fixed power supply voltage and load current but changing gap length were conducted to examine the influence of arc length.Based on the experimental results
a primary U-I characteristics study was carried out.Current variation analysis was performed to investigate the pulse patterns of the arc current for detection purposes.The results of this paper provided insights of the dc arc characteristics as well as methods for DC arc fault detection.