CHEN Kun-han, LI Shun-yao. Analysis of Over-standard Leakage Current of Lighting Arresters on a 220 kV Transmission Line[J]. High voltageapparatus, 2012, 48(5): 111-114.
CHEN Kun-han, LI Shun-yao. Analysis of Over-standard Leakage Current of Lighting Arresters on a 220 kV Transmission Line[J]. High voltageapparatus, 2012, 48(5): 111-114. DOI: 10.13296/j.1001-1609.hva.2012.05.009.
Analysis of Over-standard Leakage Current of Lighting Arresters on a 220 kV Transmission Line
Aiming at the problem of over-standard leakage current of the lighting arresters on a 220 kV line in a transformer substation
which is discovered in preventative test
the influencing factors of DC leakage current in the test are discussed
and the over-standard leakage current of the lighting arresters is found to be induced by the variation of the direct-current parameter of some resistance valve pieces in lighting arrester.Field test and dismantling analysis of the lighting arresters in the manufacturer verifies the conclusion.