WANG Qian, ZANG Chun-yan, ZHANG Ming-li. Research on the Method of Parameter Identification for Dielectric Response Equivalent Circuit of Oil-paper Insulation[J]. High voltageapparatus, 2012, 48(6): 7-11+17.
WANG Qian, ZANG Chun-yan, ZHANG Ming-li. Research on the Method of Parameter Identification for Dielectric Response Equivalent Circuit of Oil-paper Insulation[J]. High voltageapparatus, 2012, 48(6): 7-11+17. DOI: 10.13296/j.1001-1609.hva.2012.06.003.
Research on the Method of Parameter Identification for Dielectric Response Equivalent Circuit of Oil-paper Insulation
The dielectric response method is an effectively non-destructive testing method for diagnosis oil-paper insulation aging status.Identifying the circuit model of oil-paper insulation is the key to assess aging status using dielectric response method.The extended Debye model is identified by using depolarizing current of oil-paper insulation in this paper
based on the characteristics of the depolarization process of dielectric response.The multi-exponential fitting problem is simplified into a single-exponential fitting problems and the RC time constant is transformed into the slope of straight line in the identify progress by analyzing the characteristics of the depolarization process and the extended Debye model.Finally
an extended Debye model of an 110 kV transformer is identified through its depolarization current curve
using the method proposed in this paper.And a simulation is done in MATLAB.Then the 95.8% coincidence degree of simulation curve with the original curve verifies the correct of this method.