PENG Bo1, LIN Fu-chang2, HUANG Fu-yong1, et al. Protection Inductor Structure and Protection Methods for Pulsed Capacitor Banks[J]. High voltageapparatus, 2012, 48(6): 48-52+55.
PENG Bo1, LIN Fu-chang2, HUANG Fu-yong1, et al. Protection Inductor Structure and Protection Methods for Pulsed Capacitor Banks[J]. High voltageapparatus, 2012, 48(6): 48-52+55. DOI: 10.13296/j.1001-1609.hva.2012.06.011.
Protection Inductor Structure and Protection Methods for Pulsed Capacitor Banks
The protection of energy storage capacitor is important in pulse power system.The existing protection method is to use damped inductor for protecting capacitor bank.In this paper
the crack of the damped inductor in use is investigated
and the result shows that both short circuit of the capacitor and its imperfect structure may lead to crack failure.By analyzing the two causes
two corresponding methods
adding an arrester in the circuit and changing the leads structure of the inductor
are put forward to solve the problems.Experiment and simulation are conducted with the proposed methods
and the results indicate that the new inductor works well.