LU Qi-fu1, LI Xing-wang1, XU Xiao-gang1, et al. Analysis of Short Circuit Accident Analysis about for GIS Isolating Switch Disconnecting Switch Based on ANSYS[J]. High voltageapparatus, 2012, 48(8): 76-79+85.
LU Qi-fu1, LI Xing-wang1, XU Xiao-gang1, et al. Analysis of Short Circuit Accident Analysis about for GIS Isolating Switch Disconnecting Switch Based on ANSYS[J]. High voltageapparatus, 2012, 48(8): 76-79+85. DOI: 10.13296/j.1001-1609.hva.2012.08.015.
Analysis of Short Circuit Accident Analysis about for GIS Isolating Switch Disconnecting Switch Based on ANSYS
The paper discussesaking a real short-circuit accident of GIS for example.We calculated the electrical field of shield cover by ANSYS
and analyzed the influences of shield cover deformation and spring fracture caused by misalignment of moving contact and static contact of the isolating switch.It is concluded that we found GIS is very sensitive to the internal distortion of the internal electric field.When the any external factor changes the uniformity of the internal electric field of in GIS
it will lead to the electric field will exceeds the allowable value to cause insulation breakdown.