Analysis on Connection Error in Current Transformer Secondary Circuit of 500 kV Tank Circuit Breaker with Countermeasures
A hidden danger owing to connection error in the current transformer secondary circuit of 500 kV tank circuit breaker is introduced.When the 500 kV tank circuit breaker went wrong
the main protections did not trip to clear the fault because current transformer windings for respective line protection and bus protection had not been cross-connected hence two protection ranges did not overlapped and main protection did not work.The protection dead zone is found to be due to some problems in both design and installation of the current transformer through checking and analyzing the current transformer winding.Consequently
some countermeasures for avoiding the protection dead zone are suggested
such as strengthening cooperation between primary and secondary builders during design and installation stage
and paying more attention to examinations in construction