LONG Zhao-zhi~1, LU Fei~2, LEI Min~1, et al. Calculation of Ionic Flow Field for Multi-circuit HVDC Overhead Transmission Lines[J]. High voltageapparatus, 2012, 48(10): 31-36.
LONG Zhao-zhi~1, LU Fei~2, LEI Min~1, et al. Calculation of Ionic Flow Field for Multi-circuit HVDC Overhead Transmission Lines[J]. High voltageapparatus, 2012, 48(10): 31-36. DOI: 10.13296/j.1001-1609.hva.2012.10.008.
Calculation of Ionic Flow Field for Multi-circuit HVDC Overhead Transmission Lines
The calculation of ionic flow field of HVDC transmission lines is significant to transmission lines design and electromagnetic analysis
therefore
an analytical method is proposed in the paper based on Deutsch’s assumption. According to the characteristics of flux line distribution under HVDC transmission lines
the method is effective for multi-circuit lines with considering about the corona difference between positive and negative conductors.And the influence of pole arrangements is discussed.Compared with the experimental results
the results calculated by the method are match and indicated that the method has good adaptability under various lines configures.The pole arrangement of lines affects maximum total electric field at ground level hardly
but ionic current density has a great change.Without considering the other parameters of lines configure
--/++ is the best polar arrangement for doublecircuit transmission lines.And only a little effect of ground wire on ionic flow filed under multi-circuit lines.