Investigation to Over-voltage on 500 kV HVDC Double-circuit Lines on Same Tower
To understand the over-voltage level on 500 kV HVDC double-circuit transmission lines on the same tower due to the ground fault for different arrangement of conductors
and to reveal the influence of the DC overvoltage
a model of 500 kV HVDC transmission line based on concrete parameters is built by using the electromagnetic simulation software PSCAD.The over-voltage levels and distribution features on non-faulty pole with different arrangement of conductors are obtained by simulating DC line ground fault at one pole
and the best arrangement of conductors is recommended according to the simulation results.The influencing factors such as ground resistance
configuration of the DC filter and application of arresters are calculated and analyzed via simulation.The results indicate that the over-voltage level can be clearly reduced by adjusting configuration of the DC filter and applying arresters.