CHEN Qing-qi~1, ZHANG Wei-ping~1, LIU Qin-feng~1, et al. Research of Transient Earth Voltage Distribution Characteristics by Partial Discharge in Switchgears[J]. High voltageapparatus, 2012, 48(10): 88-93.
CHEN Qing-qi~1, ZHANG Wei-ping~1, LIU Qin-feng~1, et al. Research of Transient Earth Voltage Distribution Characteristics by Partial Discharge in Switchgears[J]. High voltageapparatus, 2012, 48(10): 88-93. DOI: 10.13296/j.1001-1609.hva.2012.10.017.
Research of Transient Earth Voltage Distribution Characteristics by Partial Discharge in Switchgears
TEV(transient earth voltage)technology become more and more important in HV switchgear PD detection
so
the method on how to better utilize TEV in scientific research is a priority.Based on research results on TEV principle
simulation and analysis the TEV of metal cabinet by FDTD
and switchgear partial discharge measurement on the simulation results
both with good consistency of the method describe in the simulation to obtain the feasibility of switchgear TEV signal.Based on the above method
the outer surface of a typical layout of HV switchgear forty-two test points TEV signal simulation analysis
the results show that:TEV detection signal amplitude with distance from the source point and the incentive decreases with an increase; Detection point near cracks and discontinuities
can be measured larger TEV signal;Electromagnetic interference between different switchgear is small.Switchgear for the TEV method of partial discharge detection and better use of provides a theoretical basis.