Analysis on±500 kV Gui-Guang HVDC System Open Line Test
UHVDC transmission system because of its large transmission capacity
long distance
low loss
the transmission lines just positive and negative poles lines
simple structure
small site area etc
at present in our country has been more and more widely used.This paper
from the general provisions of the no-load energization test and start wiring way
this paper expounds the principle of HVDC flow changing and open voltage calculation equation of.According to±500 kV Gui-Guang HVDC transmission system bipolar no-load energization test
compares pole 1 and pole 2 test data
draw the conclusion
there are certain asymmetry in pole 1 and 2 DC transmission lines after a long time operation
the control mode of pole 1 and 2 affects firing angle.