Analysis on Electric Field Intensity and Onset Corona Zone on the Split Conductor Surface of UHV Transmission Line
The onset corona criterion of transmission line is that the electric field intensity on conductor surface exceeds a certain critical value.In this paper
in order to study distribution of corona zones on split conductor surface
the charge simulation method is employed to calculate the electric field intensity of each matching point on the surface of a 1 000 kV UHV single-phase 8-split conductor according to the relative experimental value of onset corona voltage.The onset corona zone distribution on the conductor surface is obtained by comparing the calculated electric field intensity values with the ones from empirical formula.Furthermore
the number of onset corona points
the angle of onset corona zone
as well as the influences of conductor’s radius and height on the distribution of onset corona zones
are achieved.The results show that onset corona zones account for 30%~40% of whole conductor surface;the higher the conductor height
the larger the onset corona zone;the radius of split conductor also influences the area of onset corona zone.This study may facilitate the analysis of corona loss in transmission line.