To understand harmonics on Dongguan grid and their harm
the electric power quality analyzer FLUKE435 is adopted to carry out a survey of harmonics on capacitors in Dongguan grid.According to corresponding literatures and standards
quantitative analysis and calculation are performed for the harmonic amplification of capacitors
as well as the capacitors’ overload
incremental loss and shorter life caused by different harmonic pollution.The results show that the shunt reactive power compensation capacitors in some substations of Dongguan grid are seriously harmed by the harmonics
resulting in great waste of energy and equipment resources.