LIU Xiao-bo1, HUANG Bin2, SU Wen-yu2. Analysis and Improved Design the Overheating Problem of the Conductive Strip of GW4(A)-40.5DW Disconnectors[J]. High voltageapparatus, 2012, 48(12): 105-108.
LIU Xiao-bo1, HUANG Bin2, SU Wen-yu2. Analysis and Improved Design the Overheating Problem of the Conductive Strip of GW4(A)-40.5DW Disconnectors[J]. High voltageapparatus, 2012, 48(12): 105-108. DOI: 10.13296/j.1001-1609.hva.2012.12.021.
Analysis and Improved Design the Overheating Problem of the Conductive Strip of GW4(A)-40.5DW Disconnectors
GW4(A)-40.5DW outdoor high-voltage disconnectors are widely used in the power grid.There is a structural defect in the conductive strip of this kind of disconnectors
causing a heat conduction problem frequently.To ensure the power grid safety
the internal structure of this conductive strip structure is analyzed
and a new conductive strip is designed
implemented replacement and reform in the scene successfully.Using aluminum in the end of the conductive strip structure and welding it at a time;designing the structure of conductive strip tighten part into blot core structure;using aluminum in the soft conductive strip connection to address the existing structural defect.