BAN Jian, LI Xia, CHEN Gan, et al. Analysis on Thyristor Damaged in Single Valve Steep-front Impulse[J]. High voltageapparatus, 2012, 48(12): 109-112. DOI: 10.13296/j.1001-1609.hva.2012.12.022.
Analysis on Thyristor Damaged in Single Valve Steep-front Impulse
Due to the atmospheric correction coefficient Katm
steep-front impulse voltage on single valve is 884 kV in Q-X HVDC project valve insulation type test
the test cause 9 thyristors damaged.This article focuses on the technical specifications of the valve insulation coordination design and insulation type test technical data.It’s not necessary to calculate with Katm in single valve steep-front impulse test
and the results can assure the valve running safely at high altitudes.