GU Tie-li1, LIU Shu-qing1, ZHAO Guo-liang1, et al. Research of Anti-lightning Protective Gap Parallel with 220 kV Insulator String[J]. High voltageapparatus, 2012, 48(12): 116-120.
GU Tie-li1, LIU Shu-qing1, ZHAO Guo-liang1, et al. Research of Anti-lightning Protective Gap Parallel with 220 kV Insulator String[J]. High voltageapparatus, 2012, 48(12): 116-120. DOI: 10.13296/j.1001-1609.hva.2012.12.024.
Research of Anti-lightning Protective Gap Parallel with 220 kV Insulator String
the parallel protective gap can provide effective protection for insulator string to achieve more reliable reclosing.The current researches on the parallel protective gap in China are focused on moving characteristic of arc and shape of the gap
but few researches are concerned with the characteristics of the gap and the relationship between arc on the gap and insulator.The authors conducted a number of tests to investigate protective property of the gap to insulator
and suggested that the distance between two electrodes of the gap be large than 90% of insulator string’s structural height
and the distance between the gap and insulator string be sufficient for achieving effective anti-lightning protection of insulator string.