On-load Tap-changer Field Testing Waveform Analysis of 500 kV Electric Power Autotransformer
The M-model on-load tap-changer including 4 transient resistance has been used widely in 500 kV electric power autotransformer
the test of switching figure
transition duration and fault resistance in process of the on-load tap-changer is must been done in environmental test items of the transformer
which use to examine bridging switch function.This paper introduces the process of the M-model on-load tap-changer and characteristics of the DC circuits testing waveform of the on-load tap-changer including 4 transient resistance in 500 kV electric power autotransformer
the mechanical systems bouncing affects accuracy of the test waveform
the high-transformer affects uniformity of the test waveform
the matching factor of the instrument inner resistance with the transient resistance affects discernibility of the test waveform
need discern carefully and moreover assess for the test locale.