GAO Li-xue1, ZHANG He-shun2. Analysis of Instant Open after Close Failure with Countermeasure for CT20 Type High-power Spring Mechanism[J]. High voltageapparatus, 2012, 48(12): 143-147.
GAO Li-xue1, ZHANG He-shun2. Analysis of Instant Open after Close Failure with Countermeasure for CT20 Type High-power Spring Mechanism[J]. High voltageapparatus, 2012, 48(12): 143-147. DOI: 10.13296/j.1001-1609.hva.2012.12.029.
Analysis of Instant Open after Close Failure with Countermeasure for CT20 Type High-power Spring Mechanism
Aiming at the failure of instant open after close of CT20 type high-power spring mechanism
the authors describe the structure of the CT20 type high-power spring mechanism and the principle of maintaining closing-state
and analyzes various factors inducing the instant open after close failure.Disassembly analysis of failed mechanisms is conducted.Subsequently
tests demonstrate that the instant open after close failure of the CT20 type high-power spring mechanism is eliminated by controlling the factors mentioned.