XIAO Rong1, XU Cheng2. Analysis and Treatment of the Overheating Fault in 220 kV GW6-type Disconnector Conductive Loop[J]. High voltageapparatus, 2013, 49(1): 107-110.
XIAO Rong1, XU Cheng2. Analysis and Treatment of the Overheating Fault in 220 kV GW6-type Disconnector Conductive Loop[J]. High voltageapparatus, 2013, 49(1): 107-110. DOI: 10.13296/j.1001-1609.hva.2013.01.017.
Analysis and Treatment of the Overheating Fault in 220 kV GW6-type Disconnector Conductive Loop
many overheating faults have happened in 220 kV GW6-type disconnector conducting loop of a power plant.By mean of disassembly examination of overheating components and analysis
this paper found that the conducting surface process defects and unacceptable components size deviation are the main reasons for inducing overheating faults of this type disconnector.Solutions are put forward
which include anti-oxidized treatment of conducting surface
and using two-sided tin-plating copper belt for compensation.It has been verified in following actual operation.