SU Yong-hua, YANG Hong-feng. Ambient Temperature Effect on Partial Discharge of Capacitive Screen of Dry-type Current Transformer[J]. High voltageapparatus, 2013, 49(1): 130-133.
SU Yong-hua, YANG Hong-feng. Ambient Temperature Effect on Partial Discharge of Capacitive Screen of Dry-type Current Transformer[J]. High voltageapparatus, 2013, 49(1): 130-133. DOI: 10.13296/j.1001-1609.hva.2013.01.020.
Ambient Temperature Effect on Partial Discharge of Capacitive Screen of Dry-type Current Transformer
partial discharge is a main cause of insulation deterioration.In this paper
the partial discharge problem in dry-type current transformers is analyzed.Comparing with test data
the ambient temperature effect on partial discharge measurement level of capacitive screen of dry-type transformer is achieved.A countermeasure against the effect is proposed
with which the partial discharge measurement level of the transformer samples can return to normal by warming or electrifying them for about 20 hours.