GONG Li-qun1, LI Jing2, LONG Fu-cheng3, et al. Improvement of Protection-level Epoxy Cast Current Transformer with Special Parameters for 110 kV GIS and Measures[J]. High voltageapparatus, 2013, 49(1): 134-137.
GONG Li-qun1, LI Jing2, LONG Fu-cheng3, et al. Improvement of Protection-level Epoxy Cast Current Transformer with Special Parameters for 110 kV GIS and Measures[J]. High voltageapparatus, 2013, 49(1): 134-137. DOI: 10.13296/j.1001-1609.hva.2013.01.021.
Improvement of Protection-level Epoxy Cast Current Transformer with Special Parameters for 110 kV GIS and Measures
To improve the reliability of electrical performance and the quality of the protection-level(5P class) epoxy resin cast current transformer(CT) with special parameters
such as small transformation ratio
large load and height
for 110 kV GIS
the appearance quality and electrical performance of a batch of the protection-level epoxy cast CTs are analyzed.And corresponding solutions are suggested
including perfect dimensional coordination
reasonable selection of die structure
split-process of core
and reasonable test sequence.Experimental results demonstrate the effectiveness of the suggested solutions.