ZHAO Dan-dan1, HAN Zheng2, GUO Jie3. Grounding Modes and Electric Loss of 750 kV Overhead Ground Wire[J]. High voltageapparatus, 2013, 49(2): 67-73+79.
ZHAO Dan-dan1, HAN Zheng2, GUO Jie3. Grounding Modes and Electric Loss of 750 kV Overhead Ground Wire[J]. High voltageapparatus, 2013, 49(2): 67-73+79. DOI: 10.13296/j.1001-1609.hva.2013.02.016.
Grounding Modes and Electric Loss of 750 kV Overhead Ground Wire
the voltage level and transmission capacity of power transmission lines get larger
which results in more and more electric loss due to inductive current in ground wire and operation cost.In this paper
the amplitudes of inductive voltage and current
the electric loss of overhead ground wire
and the amplitude of overvoltage on transmission line are calculated for different grounding modes.The results show that the amplitudes of inductive voltage and current as well as the electric loss of overhead ground wire get the minimums when OPGW takes segment insulation with one point earthing
while the zero-sequence impedance and the amplitude of overvoltage become higher in this grounding mode.Both grounding modes of overall insulation and overall insulation with two ends earthing for OPGW are not recommended.