CHEN Hong-guang 1, LIU Yu-gen 2, HUANG Xiao-gang 1, et al. Application of Arc-suppression Coil in 35 kV Distribution Network[J]. High voltageapparatus, 2013, 49(3): 29-35.
CHEN Hong-guang 1, LIU Yu-gen 2, HUANG Xiao-gang 1, et al. Application of Arc-suppression Coil in 35 kV Distribution Network[J]. High voltageapparatus, 2013, 49(3): 29-35. DOI: 10.13296/j.1001-1609.hva.2013.03.007.
Application of Arc-suppression Coil in 35 kV Distribution Network
Operation data of a 35 kV distribution network were measured after XDJ1-550/35 arc-suppression coil was connected to power system.According to the parameters of the arc-suppression coil and the measurement
the percentage of displacement voltage of neutral point
the maximum unbalance degree of three-phase voltage
and the out-of-resonance degree were calculated.The analysis of the calculation results reveals the problems of difficult gear selection and insufficient capacity of the arc-suppression coil.The working process of an ACHC automatic tracking compensation device was simulated with the software ATP-EMTP