YANG Tao1, ZHAO Ke-jiang2, LIU Yu-gen3, et al. Improving Power Frequency Electric Field Distribution of Transmission Lines by Shielding Lines[J]. High voltageapparatus, 2013, 49(3): 91-98.
YANG Tao1, ZHAO Ke-jiang2, LIU Yu-gen3, et al. Improving Power Frequency Electric Field Distribution of Transmission Lines by Shielding Lines[J]. High voltageapparatus, 2013, 49(3): 91-98. DOI: 10.13296/j.1001-1609.hva.2013.03.016.
Improving Power Frequency Electric Field Distribution of Transmission Lines by Shielding Lines
Installing shielding lines under transmission lines can improve the power frequency electric field intensity under the transmission lines.According to the actual situation of the transmission lines
a three-dimensional electric field calculation model is established based on the formula of overhead catenary with sag to calculate the electric field intensity under the transmission lines with shielding lines.Some influencing factors
such as shielding lines’ height
transverse position
distance among the shielding lines
number and so on
on the power frequency electric field intensity under the transmission lines are analyzed.The results show that shielding lines can significantly improve the power frequency electric field distribution under the transmission lines.The shielding lines’ height and transverse position influence the shielding effect significantly.The distance among shielding lines has certain influence on the power frequency electric field distribution under the transmission lines.The more the shielding lines are
the better the shielding effect is
but the improvement becomes weaker.The shielding lines can enhance the surface electric field intensity of bundle conductors.