Effect Analysis on Reducing the Excessive Power Frequency Electric Field Near Buildings Close to Transmission Line of 220 kV by Using Shielding Conductors
|更新时间:2025-04-26
|
Effect Analysis on Reducing the Excessive Power Frequency Electric Field Near Buildings Close to Transmission Line of 220 kV by Using Shielding Conductors
High VoltageApparatusVol. 49, Issue 5, Pages: 44-48(2013)
WANG Kai, XU Bin, LIU Gang, et al. Effect Analysis on Reducing the Excessive Power Frequency Electric Field Near Buildings Close to Transmission Line of 220 kV by Using Shielding Conductors[J]. High voltageapparatus, 2013, 49(5): 44-48.
WANG Kai, XU Bin, LIU Gang, et al. Effect Analysis on Reducing the Excessive Power Frequency Electric Field Near Buildings Close to Transmission Line of 220 kV by Using Shielding Conductors[J]. High voltageapparatus, 2013, 49(5): 44-48. DOI: 10.13296/j.1001-1609.hva.2013.05.010.
Effect Analysis on Reducing the Excessive Power Frequency Electric Field Near Buildings Close to Transmission Line of 220 kV by Using Shielding Conductors
This paper is about studying on reducing the power frequency electric field producing by the high tension transmission line near the buildings open field.Using a 220 kV high level line and the high building near it
the paper studies on the shielding effect of setting up balcony shielded wire.First
this paper surveys the electric pollution of the building near the high tension transmission line by site investigation and simulation analysis. Then
after making the balcony shielded wire model by simulation software
this paper analyses the influence of shielding effect when changing wire diameter and clearance of shielded wire
horizontal distance and vertical distance of the shielded wire with balcony and integrity of the shielded wire.Studies have shown that setting up balcony shielded wire can effectively reduce the power frequency electric field of balcony
which dropped to less than 30% of the original.At the same time
using of the integrated shielded wire which has greater wire diameter
smaller clearance
farther from the balcony edge of the horizontal distance and vertical distance works best.