ZHANG Wu-jie, ZHANG Shu-qin, ZHANG Ke-xuan, et al. Problems and Solutions Related to GIS Site Direct Connection[J]. High voltageapparatus, 2013, 49(5): 114-119.
ZHANG Wu-jie, ZHANG Shu-qin, ZHANG Ke-xuan, et al. Problems and Solutions Related to GIS Site Direct Connection[J]. High voltageapparatus, 2013, 49(5): 114-119. DOI: 10.13296/j.1001-1609.hva.2013.05.021.
Problems and Solutions Related to GIS Site Direct Connection
design and manufacture of miscellaneous high voltage devices are more and more perfect and gradually formed their own complete quality control system nowadays.But problems in the connection between different equipment onsite appear continuously due to different manufacturers supply different main equipement.Common main equipment connected to GIS are power transformer(or reactor)
power cable and gas insulated lines(GIL) etc.This paper explains main points of direct connection mode and gives feasible measures.Direct connection docking part shall be set to detachable independent gas chamber
its interface size and supply division shall enough be communicated within different manufacturers or utilities.In this paper
the problems and solutions of direct connections of GIS to transformer
cable and GIL are analyzed such as connection size