Fault Judging Method for SF6 Gas Insulated Switchgear via Measuring Hydrolysable Fluoride with Ion Chromatography
Ion chromatography is used for measuring hydrolysable fluoride in sulfur hexafluoride(SF6) gas to understand the variation trend of hydrolysable fluoride in SF6 gas in the case of simulated discharge and overheating.The volume fractions of the hydrolysable fluoride in both normal and faulty SF6 insulated equipments are obtained.Accordingly
the reference values of hydrolysable fluoride content for judging the fault in SF6 insulated equipment is given.