YE Hai-feng 1, QIAN Yong 1, MAN Yu-yan 2, et al. Simulation Analysis of Transient Earth Voltages Aroused by Partial Discharge in Switchgear[J]. High voltageapparatus, 2013, 49(7): 13-17+24.
YE Hai-feng 1, QIAN Yong 1, MAN Yu-yan 2, et al. Simulation Analysis of Transient Earth Voltages Aroused by Partial Discharge in Switchgear[J]. High voltageapparatus, 2013, 49(7): 13-17+24. DOI: 10.13296/j.1001-1609.hva.2013.07.006.
Simulation Analysis of Transient Earth Voltages Aroused by Partial Discharge in Switchgear
The mechanism of transient earth voltages(TEV)aroused by partial discharge in switchgears is analyzed.The Finite Integration Theory(FIT) was employed to simulate the propagation of TEV in the switchgear.The simulation results show that the pulse width of TEV increases as the pulse width of PD pulse increases
and the amplitude of TEV is proportional to the PD pulse amplitude.There are time differences between the TEV signals of different detecting points when the TEV propagating on the switchgear’s surface.Based on the simulation
a method of locating the PD in switchgear is proposed by positioning multi-sensors on the external surface of switchgear.
Simulation and Experimental Study on Partial Discharge Decomposition Components of Air-insulated Switchgear Cabinet Considering the Influence of Temperature and Humidity
Research on the Influence of Temperature and Humidity on the Physical Signal of Partial Discharge of Switchgear
RESEARCH ON THE CHARACTERISTICS OF ULTRASONIC SIGNALS OF PARTIAL DISCHARGE IN 12V SWITCHGEAR CABINET
On-line Detection and Location of GIS Partial Discharges by UHF Sensing
变压器局部放电在线监测中的自适应滤波技术研究
Related Author
JI Hongquan
XIN Feng
LIU Ruoxi
WANG Zhihui
LUO Zhongge
GUI Yuan
CAI Lehui
ZENG Chaoxu
Related Institution
Power Research Institute of State Grid Beijing Electric Power Co., Ltd.
State Grid Beijingg Electric Power Company
State Grid Beijing Electric Power Company Urban Power Supply Company
Chengdu University of Technology
College of Electrical Engineering, Sichuan University