WANG Zi-bo. Study on the Discharge Characteristics on Basin-type Insulator Surface in GIS[J]. High voltageapparatus, 2013, 49(8): 56-59+67. DOI: 10.13296/j.1001-1609.hva.2013.08.011.
Study on the Discharge Characteristics on Basin-type Insulator Surface in GIS
Gas insulated switchgears occupy an important position in the power system.Insulating spacers are important parts in GIS.A research on the surface discharge characteristics of the GIS spacer is presented in this paper
and the ultraviolet imaging technology
ultrasonic testing technology and pulse current method to test the whole discharge process are used.Based on the data analysis
the following conclusions are obtained: ① Ultraviolet photons indicator shows the "saturation" characteristic
which occurs at the voltage up to 68 kV
then ultraviolet photon number increase is not obvious even the voltage increases after 68 kV;② To the defect near to the spacer
as discharge intensifies
charged particle collision more intense
so the heat increase results in local volume expanding rapidly
the pressure increase leads to enhance the ultrasonic signal.These works provide a valuable reference for follow-up PD study of GIS.