Ultraviolet Image Facular Area Vary Characteristic and Apparent Discharge Estimation of Suspension Composite Insulator Corona
the discharge facular region in the ultraviolet(UV) images was extract with digital image processing algorithm
and the facular area parameter was defined
in the high voltage laboratory
the corona discharge character at the high voltage side of 10 kV
35 kV and 110 kV composite insulator were studied
the relation curves of facular area and apparent discharge was obtained.The corresponding experiment data was fitted with the CFTOOL function toolbox in MATLAB
research showed that the facular area to gain had approximate exponential relationship
and the facular area to the observe distance had approximate power function relationship.On that basis
this paper established the curves of facular area with the distance under different discharge intensity with the gain was 50%
60%
70% and 80%
then a discharge quantification estimation model is established with the LS-SVM(least squares support vector machine
LS-SVM) regression algorithm
testing showed that it has good prediction accuracy.