ZHANG Qiang, WANG Wei-qing. Study on Short-circuit Faults During LVRT in Wind Farm[J]. High voltageapparatus, 2013, 49(8): 74-80. DOI: 10.13296/j.1001-1609.hva.2013.08.013.
Study on Short-circuit Faults During LVRT in Wind Farm
To analyze the short-circuit faults occurred in wind farm system while power system voltage drops
a mathematical dynamic model and a steady-state model of wind farm with DFIG are established in the synchronous rotary coordinates.In the condition of continuously connecting wind farm to grid and keeping power generation on the MATLAB/SIMULINK platform
the LVRT ability of wind farm without short-circuit fault or with short-circuit faults in some generators is analyzed
and wavelet-based fault analysis is performed.With simulation
some main electrical parameters are easily obtained.Conclusions can be drawn from the simulation results that: steady LVRT of wind farm system can be completed in the condition of single phase short-circuit fault;while the situation gets worse for two-phase or three-phase fault
where voltage recovers within a moment
and both wind farm and power system will endure a great deal of energy flow.So the faulty phase should be cut off before voltage recovery.