Research on Switching Induced Voltage and Current by Earthing Switch in 500/220 kV Four-circuit on One Tower
Multi-circuit on one tower for electric transmission lays high restrictions on the earthing switch.The authors take the 500 kV Zhen-Bao double lines and the 220 kV Dong-Pu double lines on one tower as an example to analyze the induced voltage and current
and calculate the induced voltage and current of the 220 kV Dong-Pu double lines with the software ATP-EMTP(Alternative Transients Program-Electromagnetic Transients Program).The results show that the induced voltage and current exceed the values of B class of earthing switch.Further
they conduct a test of switching the Ultra-B class induced voltage and current on the 220 kV JW6-252/J50 earthing switch in 500 kV Dongguan Transformer Substation.Obvious arc phenomenon is observed in the earthing switch in breaking the induced voltage of 2.7 kV and the induced current of 236.9 A.After 10 times of breaking
the surface of the moving contact is still smooth without ablation.And the switching time of the earthing switch keeps consistency before and after the test
meeting the design requirement.Test results indicate that this type of earthing switch can effectively switch required induced voltage and current.
Calculation and Measurement Analysis for Induced Voltage and Current of 500 kV/220 kV Mixed-voltage and Four-circuit Transmission Lines on the Same Tower
Induced Current Switching Tests of the Earthing Switches in Type ZFW-500 CIS
Application of Class B Earthing Switch Switching Induced Current in Gezhouba Hydropower Station
Study on Calculation and Measurement of Induced Voltage and Induced Current Between 750 kV Double-circuit Parallel Lines
Simulation Analysis for Induced Voltage and Induced Current in the Oil & Gas Pipeline Parallel Under 500 kV AC Double-circuit Transmission Lines on Same Tower
Related Author
HUANG Shiyang
NING Linru
CHEN Xiao
WANG Chenxing
LIN Tao
PENG Zhaowei
XU Dangguo
LI Yamei
Related Institution
Beijing Power Transmission and Transformation Co., Ltd.
State Grid Jibei Electric Power Co., Ltd.
State Grid Jibei Electric Power Co., Ltd. Electric Power Science Research Institute