ZHAO Qing-bin, HUANG Shi, WU Zhao. Computation and Comparison of Current Parameters of Asymmetrical Current Breaking for Generator Circuit Breaker[J]. High voltageapparatus, 2013, 49(9): 113-118.
ZHAO Qing-bin, HUANG Shi, WU Zhao. Computation and Comparison of Current Parameters of Asymmetrical Current Breaking for Generator Circuit Breaker[J]. High voltageapparatus, 2013, 49(9): 113-118. DOI: 10.13296/j.1001-1609.hva.2013.09.019.
Computation and Comparison of Current Parameters of Asymmetrical Current Breaking for Generator Circuit Breaker
The current parameters of asymmetrical current breaking of a generator circuit breaker are calculated with the DC time constant of 150 ms via Microsoft Excel and dichotomy.By analyzing the alternative and direct components
the current formula for last-pole-to-clear condition is derived.According to the calculation of the current parameters and the comparison between the standards IEC 62271-37-013 and GB/T 1984 —2003 for generator circuit break(GCB) asymmetrical current tests
it is concluded that the IEC 62271-37-013 under discussion is more reasonable as it takes the current parameters for last-pole-to-clear condition into consideration.