WANG Jing-jun, HUANG Yu-long. Analysis on an Insulation Breakdown Accident of 500 kV GIS Disconnector[J]. High voltageapparatus, 2013, 49(9): 119-123. DOI: 10.13296/j.1001-1609.hva.2013.09.020.
Analysis on an Insulation Breakdown Accident of 500 kV GIS Disconnector
An accident of insulation breakdown of a 500 kV GIS disconnector is introduced.The fault current and the SF6 content are analyzed
the faulty disconnector is disassembled
and the solid decomposition product is observed by SEM.It is found that the insufficient moment of the screw on the equalizing ring due to poor assembly process increases the contact resistance
which results in heating and melting of the screw to cause the accident.