Analysis and Study on Displacement Transducer for Testing in Mechanical Test of Intelligent High-voltage Switch
based on comparsion of the different characteristics between the traditional high voltage switchgear and intelligent high voltage switchgear
together with the state grid guidance of intelligent high-voltage switch test
as well as the national standard GB 1984—2003
the purpose of this paper is to analysis the influences of displacement transducer on mechanical performance test result of intelligent high-voltage switch. These influences include the selection of transducer type
the arrangement location and the arrangement method of transducer. Results show that
in order to promote the accuracy of parameters of mechanical test
the transducer should be arranged in a component of test CB
which could exactly reflect the motion of contacts. Moreover
to facilitate the intelligent breaker in the type test of mechanical properties
it should be considered that the selected interface protocols of transducer match with the test system.