Influence Analysis of Conductor Surface Maximum Electric Field Strength on DC Transmission Line Electromagnetic Environment
The calculation method of the HVDC transmission line conductor surface maximum field strength and electromagnetic environment parameters. For ±660 kV DC transmission line
the influence of the conductor surface maximum field strength on the ground synthetic electric field
the ground ion current density
radio interference and audible noise were analyzed. When the positive conductor voltage is between 620 kV to 680 kV
with the increase of the conductor surface maximum field strength
the synthetic ground electric field and ground ion current density increase by 1.2 times and 2.8 times. The influence on the radio interference and audible noise are relatively small
and the increased values are17% and 0.3% respectively. When the ±660 kV DC transmission line is under rated voltage
the electromagnetic environmental indicators will not exceed the specified value in high voltage direct current overhead transmission line technical guidance.