JIN Song-an, LIU Chao-feng, WU Sheng-bin, et al. Seismic Behavior Analysis of Disconnectors in High Altitude Area[J]. High voltageapparatus, 2013, 49(10): 37-45.
JIN Song-an, LIU Chao-feng, WU Sheng-bin, et al. Seismic Behavior Analysis of Disconnectors in High Altitude Area[J]. High voltageapparatus, 2013, 49(10): 37-45. DOI: 10.13296/j.1001-1609.hva.2013.10.010.
Seismic Behavior Analysis of Disconnectors in High Altitude Area
As a key component of power transmission and distribution systems
disconnector have suffered serious damage in previous earthquakes. Generally
typical destruction feature of disconnector during earthquakes appears as the breaking at bottom of insulator porcelain posts. In this paper
taking a typical252 kV disconnector as an example
study the seismic behavior of 3 km-altitude disconnector on finite element and compare with low-altitude disconnector. The two kind of disconnector can’t be satisfy earthquake-resistent design of AG5.