Application of Variable Frequency Power Supply Method to In-site ACLD Tests of 1 000 kV UHV Transformer
This article describes the partial discharge test in-site for 1 000 kV power transformers taking a variable frequency power supply as the test power source. The performance parameters and testing process of a 1 000 kV power transformer are analyzed. The whole test circuit is computed for validation
and the computation result is compared with the measured data. In addition
some anti-interference measures
such as detecting and locating partial discharge with ultraviolet
multipoint earthing of test circuit
and adding isolation transformer to test power source
are offered. This partial discharge test method has the advantages of smaller test equipment and flexible connection
and is worth while to propagate in ultra-high voltage projects.