JIN Bai-rong, LI Dian, CAI Zhong-kai. Control of Switching Overvoltage for 35 kV Shunt Reactor[J]. High voltageapparatus, 2013, 49(10): 64-71. DOI: 10.13296/j.1001-1609.hva.2013.10.013.
Control of Switching Overvoltage for 35 kV Shunt Reactor
To control the switching overvoltage caused by switching off shunt reactor in 35 kV system
simulation and evaluation with the software ATP-EMTP
10 kV laboratory test
and on-site test in 35 kV system were conducted to investigate the control of switching overvoltage. The treatments
such as circuit breaker switching at the side of neutral point of shunt reactor
and paralleling MOAs via shunt reactor
were verified through field experiments. The results indicate that the circuit breaker switching at the side of neutral point of shunt reactor can control the switching overvoltage effectively. In addition
the validity and applicable range of other treatments are discussed.
Study on Oil Temperature Prediction of Shunt Reactor Based on Feedback Constrained Variational Mode Decomposition and Long Short-term Memory Neural Network
The Analysis on Whether ZnO Surge Arrester Can Protect H.V. Motor from Damage Caused by Switching Overvoltage of Vacuum Circuit Breaker
Overvoltage Calculation for Elimination of Closing Resistors in Tieling 500k V Power System
APPLICATION OF TBP TO THE SUPPRESSION OF SWITCHING OVERVOLTAGE IN MEDIUM VOLTAGE MOTOR
STUDY ON THE OVERVOLTAGE FOR THE330kV POWER TRANSM ISSION PROJECT OF GONGBO GORGE
Related Author
CHEN Haoyu
CAI Lichuan
DING Wentao
DAN Shuheng
Shang Zhenqiu
施围
牛晓民
陈亚伦
Related Institution
State Grid Sichuan Electric Power Company
College of Electrical Engineering, Shanghai University of Electric Power