GIS Partial Discharge Detection via Ultra-high Frequency Signal in Lightning Impulse Process
The effectiveness of detecting GIS partial discharge(PD) via ultra-high frequency(UHF) signal in lightning impulse process was investigated experimentally. In this scheme
No.1 UHF sensor detected the electromagnetic wave signal around the impulse voltage generator for the reference signal; No.2 UHF sensor detected the signal radiating from the basin-type insulator. The results show that: ① By comparing the waveforms from the two sensors
PD signal can be distinguished from the interference signal; ②When PD happens in GIS
the signal from No.2 UHF sensor exhibits three pulse groups with different signal amplitude
density and distribution; ③PD signal appears at 4 μs after PD pulse starting
and it continues for about 5 μs. Conclusion can be drawn that the UHF method is effective and reliable for GIS PD detection in lightning impulse process.