DU Zhen-bo, NIE De-xin, ZHANG Lian-xing, et al. Insulation Evaluation of High Voltage Bushing Based on Frequency Domain Spectroscopy Analysis[J]. High voltageapparatus, 2013, 49(11): 6-11.
DU Zhen-bo, NIE De-xin, ZHANG Lian-xing, et al. Insulation Evaluation of High Voltage Bushing Based on Frequency Domain Spectroscopy Analysis[J]. High voltageapparatus, 2013, 49(11): 6-11. DOI: 10.13296/j.1001-1609.hva.2013.11.004.
Insulation Evaluation of High Voltage Bushing Based on Frequency Domain Spectroscopy Analysis
To develop new on-site insulation detection method of high voltage bushings and improve the diagnostic accuracy
three oil-immersed paper insulated high voltage bushings with same structure were tested with the frequency domain spectroscopy(FDS) method in dielectric response theory. FDS test was conducted under different temperature
paper moisture content and thermal aging time to obtain the dielectric loss frequency curves.The dielectric loss frequency curves within 0.01
1
000 Hz were used to evaluate the water content of the bushings.The results show that the dielectric loss frequency curves
in lower frequency range are more sensitive to moisture content of the paper insulation due to the effects of temperature
and aging time. The analysis of paper moisture content via FDS measurement can also help to evaluate aging and moisture conditions of the bushing. Compared with conventional power frequency dielectric loss measurement
the FDS measurement is more sensitive to insulation aging and moisture condition in a high voltage bushing.
Insulation Condition Evaluation of 750 kV Power Transformers Based on Frequency Domain Spectroscopy
Method on Distinguishing Aging and Deterioration Condition of Insulation and Semi-conductive Materials via Channel Characteristics of Medium Voltage Cable
Research on High Temperature Corrosion Characteristics of Lamella of HV Bushing in SF6 Atmosphere
Study on Mechanical Property Variation of EPDM Sealing Materials for GIS Equipment Before and After Aging
ANALYSIS ON THE EVALUATION METHOD OF AGING FOR COMPOSITE INSULATORS
Related Author
YANG Shuang-suo1
ZHANG Guan-jun1
DONG Ming1
WEI Jian-lin1
WANG Shi-qiang1
YU Zheng2
FENG Yu-Chang2
CHEN Jie
Related Institution
Northwest China Grid Company Limited,Xi′an
State Key Lab.of Electrical Insulation for Power Equipment,Xi′an Jiaotong University,Xi′an
Wuhan Branch of China Electric Power Research Institute Co., Ltd.
State Grid Jiangsu Electric Power Co., Ltd. Electric Power Research Institute
State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University