which often conflicts with the protective operation box in function. If the control circuit cannot coordinate with the box
the safe and stable operation of power grid and circuit breakers will be affected. In this paper
the characteristics of anti-tripping circuit
low-pressure locking of tripping and closing
and non-whole-phase protection circuit are analyzed and summarized. Some methods for their coordination are proposed
such as connecting a contact of "Local/Remote" switch handle ZK in the ant-tripping circuit in mechanism box; the functions of low-pressure locking tripping
closing and operating being implemented by the breaker body; only first operating power being selected for low-pressure locking of reclosure circuit; and adopting non-whole-phase protection in the breaker body
while taking the electrical quantities based non-wholephase protection as a supplement. These methods may enhance reliable operation of the circuit breaker to ensure the safe and stable operation of the power system.