Characteristics of Surface Partial Discharge on Joint of Insulated Copper Busbar
Insulated copper busbar is widely used in power grid in recent years. However
surface partial discharge often happens on its joint. In this paper
the characteristics of the surface partial discharge on the joint are studied.A surface discharge model of the insulated copper busbar joint is constructed in laboratory. The initial discharge voltage and the features of discharge spectrum for different distances between discharge point and earthing panel are investigated with the model. The results show that the initial voltage and amplitude are low and the discharge spectrum is symmetrical when the discharge point is close to the earthing panel. This study may provide a basis for early detection of surface discharge on insulated copper busbar joints.