LI Yan-peng, JIN Tao, ZHANG Jian. Application of Ultraviolet Imagery Technology in Partial Discharge Measurement Test of UHV Transformer[J]. High voltageapparatus, 2013, 49(11): 123-126+132.
LI Yan-peng, JIN Tao, ZHANG Jian. Application of Ultraviolet Imagery Technology in Partial Discharge Measurement Test of UHV Transformer[J]. High voltageapparatus, 2013, 49(11): 123-126+132. DOI: 10.13296/j.1001-1609.hva.2013.11.022.
Application of Ultraviolet Imagery Technology in Partial Discharge Measurement Test of UHV Transformer
Jindongnan-Nanyang-Jingmen 1 000 kV UHVAC transmission project is the project of the largest capacity and the highest voltage level in the world. Most of its UHV electric equipment handover tests are the first.Especially for the partial discharge(PD)test of 1 000 kV transformer
better anti-interference measurement method is required due to the conditions of higher test voltage
complex field environment
and higher standard. In this paper
the detection of external corona interference by ultraviolet imaging technology in the PD test of 1 000 kV transformer is introduced. With the detection method
the external interference in the PD test can be located rapidly and accurately
thus the interference can be eliminated to ensure successful PD test.