Waveforms Analysis and Over-voltage Calculation of Lighting Trip-out of Double-circuit Power Transmission Line on Same Tower
several failures of double-circuit power transmission line on same tower due to lighting have happened. Although the transmission line can be reclosed successfully
the lighting strike is still a threat against the power grid security. In this paper
taking the Xi-Long 110 kV double-circuit power transmission line on same tower as an example
the relay protection action and recorded fault waveforms are analyzed
and the over-voltage level on the insulator strings is calculated. Based on the analysis and the calculation
the generation and development of the accident are deduced
and its cause is described. Conclusion is drawn that the lighting accident concerned terrain feature
large corner towers
strong thunderstorm weather and poor grounding contact of the tower.