LI Jun-hao, HOU Xin-yu, LI Hai-tao, et al. Case Study of a Discharge Fault in 110 kV GIS PT Chamber[J]. High voltageapparatus, 2013, 49(12): 141-144. DOI: 10.13296/j.1001-1609.hva.2013.12.026.
Case Study of a Discharge Fault in 110 kV GIS PT Chamber
A discharge fault in a 110 kV GIS PT chamber was investigated via measurement of SF6decomposition products and UHF partial discharge detection. A variety of SF6decomposition products at high level were found in the chamber. UHF partial discharge detection indicated a discharge amplitude of over-20 dBm. Disassembly inspection showed that the discharge was generated by the floating potential due to poor contact between the shield plate at C-phase side and the core clamp in the PT gas chamber.Accordingly